← All Advisories
Reported from OT-Advisories.com as of

CVE-2026-110022

Last refreshed2026-11-04

Status: UPDATED  |  Advisory ID: CVE-2026-110022

Key Details

CVECVE-2026-110022
CVSS Score / Version
8.4 (High) / CVSS v3.1
Updated2026-11-04
CVSS Vector
CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS Prose
attack vector is local; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is high.
Affected products
Phoenix Contact PLCnext Engineer
Classified as
CWE-494 (Download of Code Without Integrity Check)

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
Phoenix ContactPLCnext Engineer
SubsystemsGeneral OT
SectorsMultiple

What to Know

The PFI plugin framework deploys executable assemblies (DLLs) from a signed plugin package into the local plugin repository and loads them via reflection, but the deployment routine processes archive entries that were never covered by the signature verification. An unauthenticated local attacker can replace an unsigned DLL outside the signed prefix in the archive passes verification and overwrites the legitimate signed assembly at the same destination path. The plugin loader then instantiates the attacker-supplied code without any additional integrity check resulting in a full compromise of the affected systems. (NVD)

What to Do

Monitor Phoenix Contact's web page for any future patch releases. See vendor advisory link below.

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-110022
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-110022
Vendor advisoryhttps://www.certvde.com/en/advisories/VDE-2026-121/